Home View Cart Site Map Contacts
 
Study Shows Dramatic Decreases in Particle Counts in School with Mechanical Ventilation
By Jim Rosenthal, 2/12/2010

This study shows that a school with mechanical ventilation and a variable volume make-up air system has one-eighth the particulate level of outdoors.

Health professionals often recommend that asthmatics and others with respiratory diseases stay indoors during periods of high outdoor air pollution. Components of pollution such as Ozone, various Nitrogen compounds and particulate matter have all been shown to have negative effects on these individuals. However, there is the potential for outdoor to indoor transfer and the question arises as to just how beneficial "staying indoors" really is. What protection does an indoor environment afford?

Most children spend a significant portion of their time in school buildings. To what extent does the typical school environment lessen exposure to outdoor air pollution? A recent study conducted by researchers from the University of Utah gives us some information on this question. In an article published in the Journal Indoor Air, Parker et al. analyze indoor particle counts in a school and compare them to outdoor particle counts in the playground of the same school. The school has a variable air volume HVAC system with return air and fresh air intake . The make up air is controlled by a CO2 monitor set at 800-1,000 ppm. The study took place at a school in Utah in January and February so only the heating portion of the system was used. MERV 8 filters were used in the HVAC units. The system was designed so that both the return air and the outside air pass through the filters.

MERV 8 filters have an average particle size efficiency of 70% or more in the particle sizes between 3 and 10 micrometers (E3). They are not assessed on their ability to collect particles in the 0.3 to 1 micrometer range (E1) or the 1 to 3 micrometer range (E2). This does not mean that MERV 8 filters do not capture particles in these ranges. It only means that the filter efficiency levels in these smaller groups are not used to calculate the final MERV number for a filter. It is important to understand that all filters capture at least some particles in all size ranges. It is only those filters with a MERV 9 and above that are assessed on efficiency by particle size in the 1 to 3 micrometer range and MERV 13 that are assessed on their efficiency on particles in the 0.3 to 1 micrometer range.

Particle counts were taken on five of the most polluted days and five of the least polluted days. It is very interesting to see the particle counts in this school as they compare to outside particle counts in all particle size ranges. They are very informative in that they show the effects of the protection of the building envelope and the HVAC system filter efficiency.

Measurements of particle mass at PM2.5 showed that indoor mass was 10% of outdoor mass when the building was "occupied." When the building was "not occupied" the indoor particle mass at PM2.5 was 6% of the outdoor particle mass. In the 6 size ranges from 0.3 to 1.6 micrometers both the "occupied" readings and the "non-occupied" readings were about 10% of outdoor particle counts. But starting at the 1.6 micrometer range the "occupied" readings start to exceed the "non-occupied" readings. At 1.6 micrometers the "occupied" count is 35% of the outdoor count while the "non-occupied" count is 15% of the outdoor count. On particles between 4 and 5 micrometers the "occupied" count is 52% of the outdoor count while the count in this size range when the building is vacant is 2% of the outdoor count. When particles go up to the 7.5-10 micrometer range the indoor "occupied" count is actually 11.3 times (1130%) the outdoor count while the vacant building count is 20% of the outdoor count.

While the combination of the building envelope and the HVAC system do a good job of reducing particles in the smaller size ranges, the movement of the many people in the school add significantly to the larger particle counts. Many allergens are 5 micrometers and above and it is likely that the resuspension of larger particles could lead to higher allergic reactions in a school environment. Other studies have shown that cat dander is present on the clothes and hair of students who do not have cats in their homes and have no direct contact with cats. Presumably those students with cats at home have cat dander on their clothes and transport it into the school environment.

Another interesting point of the study is that even a MERV 8 filter can be relatively effective at reducing particles of PM2.5 and below. As mentioned above even though a MERV 8 filter does not have to meet a set level of efficiency on particles below 3 micrometers to be a MERV 8, they are effective at removing smaller particles. For example, it is typical that a MERV 8 filter will capture over 60% of the particles at 2 micrometers and 50% of the particles at 1 micrometer. Since much of the air inside a building is recirculated through the HVAC system whenever the unit is running, it is likely that most air will go through the filter multiple times and reduce particles on each pass.

This study is limited in that it only covers one school and only applies to the experience in one geographic area at one time of the year. However, it does give us an interesting glimpse at particles in schools and may explain some of the environmental reactions of students, faculty and administrative personnel in school enviroments.

News & Announcements

Children in Neighborhoods Near Highways and Railroad Intersections at Risk for Asthma
A study by Mayo Clinic shows that children living near traffic intersections at greater risk of developing asthma.

Study Shows Dramatic Decreases in Particle Counts in School with Mechanical Ventilation
This study shows that a school with mechanical ventilation and a variable volume make-up air system has one-eighth the particulate level of outdoors.

Tex-Air Filters Purchases Pure Air Filter Company of Dallas
The New Location of Tex-Air Filters at 2324 Merrell in Dallas Gives More Convenient Service to Metroplex Customers. Pictured above left to right are Benny Aycoth, Dallas Regional Manager, Stevan Brown, President and Jim Rosenthal, Chairman

Do Some Air Filter Materials React With Ozone to Create Building Related Symptoms (BRS)?
Does a Recent Analysis of BASE Data Really Show a Connection Between Synthetic Air Filters and (BRS) or Sick Building Syndrome?

Researchers Confirm Some Air Cleaners Generate Ultrafine Particles
A University of Texas Study confirms that some air cleaners actually increase ultrafine particles and formaldehyde.

Comparative Tests on Pressure Drop of HVAC Filters
We test 20 filters for pressure drop and efficiency.

Saline Rinse May Cut Cold and Flu Symptoms
Cold medications are out for children. Simple saline rinse could be the answer for quicker recovery from colds and flu.

Sorting Fact from Fiction on Health Effects of Mould
Leading Asthma and Allergy Experts Discuss the Most Recent Scientific Evidence on Health Effects of Mould

What is a Safe Level of Ozone for an Air Cleaner?
The Consumer Product Safety Commission (CPSC) is trying to answer this question. Their study and the responses to that study highlight the complexity of the issue.

Study on Photocatalytic Oxidation (PCO) Raises Questions About Formaldehyde as a Byproduct in Indoor Air
Research at Lawrence Berkeley National Laboratory finds that Photocatalytic Oxidation (PCO) reduces indoor VOC's but could produce formaldehyde as a byproduct.

Study Finds RCI Devices Increase Indoor Ozone and Are Relatively Ineffective at Particle Removal
This study shows that the RCI (radiant catalytic ionization) Air Cleaning Devices produce fairly significant levels of ozone and are less effective than a standard air filter at removing 2 micron sized particles.

Improving Indoor Air Quality in Classrooms Leads to Higher Test Scores
This study shows that improved indoor air quality in classrooms leads to higher test scores for students.

Study Shows Increased Inflammation in Asthmatics Exposed to Air Pollution
Fine particles in air pollution shown to increase nasal inflammation in asthmatic children.

Studies Show Improved IAQ Leads to More Productivity
Numerous studies show that improving the Indoor Air Quality will lead to higher worker productivity. Measures to improve IAQ don't cost - they pay!!

The Indoor Air Thickens - New Study Confirms Links with Ozone, Cleaning Agents and Air Contaminants
Fine particles, formaldehyde and other air contaminants are created when common cleaning agents are exposed to indoor ozone.

Isn't it Ionic? Air Purifiers Make Smog
Another study confirms that ionizers and ozone generators can create unhealthy levels of ozone in poorly ventilated rooms.

Do Air Filters Provide Health Benefits?
Air cleaners and air filters alone have not been shown to be clinically effective at reducing allergy symptoms.

Alchemy, Indoor Air and the Black Box
Be wary of excessive marketing claims for products to take care of indoor air.

Free Radicals Are NOT "Friendly Oxidizers"
Some new air cleaning devices are using free radicals or Reactive Oxygen Species (ROS) to "oxidize" indoor air. Free radicals have been shown to be damaging to human health. Testing is lacking on the by-products of the reactions between free radicals and the components of indoor air.

NAFA Expands Air Filter Specialist Program
Only Filter Certification now open to all individuals interested in air filters and indoor air quality.

Avian Flu Filtration Precautions
Proper filtration can help to minimize the risk of spreading the flu virus.

Is there such a thing as Toxic Mold?
Study does not confirm "toxic mold syndrome" in patients

HEPA Air Cleaners Shown to Reduce Asthma Symptoms When Used in Conjunction with Other Control Measures
Inner City Asthma Study shows effectiveness of comprehensive environmental controls including air purifiers to control asthma.

Filter Needs in the LEED Rating System
Building owners obtain points in LEED system with proper filtration.

Proper Filter Installation Ensures Maximum Performance
Gaps between filters can cause significant decreases in filter efficiency.